Details
DESCRIPTION
NAYRY cable is suitable for AC 50Hz power and distribution lines with rated voltage of 0.6/1kV, which can be used in fixed industrial power applications, underground tunnels, etc. Using steel wire armour offers great mechanical protection, making it rigid with a large radius.

APPLICATION
All Aluminium Conductors are used for aerial distribution lines having relatively short spans, aerial feeders and bus bars of substations.

STANDARD
IEC 60228 Conductors IEC 60502-1 Power cables with extruded insulation and their accessories for rated voltages from 1kV(Um=1.2kV) up to 35kV(Um=40.5kV) - Part 1: Cables for rated voltages of 1 kV(Um=1.2kV) and 3 kV(Um=3.6kV).
DOWNLOAD
CABLE DATASHEET
Specifications
N/A
IEC 60228 Conductors IEC 60502-1 Power cables with extruded insulation and their accessories for rated voltages from 1kV(Um=1.2kV) up to 35kV(Um=40.5kV) - Part 1: Cables for rated voltages of 1 kV(Um=1.2kV) and 3 kV(Um=3.6kV).
I DISTRIBUTION LINE
SUBSTATION
N/A
N/A
Refer to relative standards
N/A
N/A
Other Properties
N/A
Open air
N/A
BY WOODEN OR STEEL-WOODEN OR FULL STEEL REEL/DRUM
AAC Cable

CONSTRUCTION

1. Conductor:

Hard drawn aluminum wire

Generally, the AAC Conductor is formed by the following construction:

AAC Cable
parameter
IEC 61089
DIN 48201-5
AS 1531
BS 215-1
BS EN 50182
ASTM B 231/B 231M
GB/T 1179
Code
Name
Nominal
Area 
No. & Dia. of Wire Approx. Overall
Dia.
Approx.
Weight
Nominal Breaking
Load
Max. DC Resistance
at 20°C
mm2 No./mm mm kg/km kN Ω/km
10 10.0  7/1.35 4.05  27.4  2.0  2.8633 
16 16.0  7/1.71 5.13  43.8  3.0  1.7896 
25 25.0  7/2.13 6.39  68.4  4.5  1.1453 
40 40.0  7/2.70 8.10  109.4  6.8  0.7158 
63 63.0  7/3.39 10.17  172.3  10.4  0.4545 
100 100.0  19/2.59 12.95  274.8  17.0  0.2877 
125 125.0  19/2.89 14.45  343.6  21.3  0.2302 
160 160.0  19/3.27 16.35  439.8  26.4  0.1798 
200 200.0  19/3.66 18.30  549.7  32.0  0.1439 
250 250.0  19/4.09 20.45  687.1  40.0  0.1151 
315 315.0  37/3.29 23.03  867.9  52.0  0.0916 
400 400.0  37/3.71 25.97  1102.0  64.0  0.0721 
450 450.0  37/3.94 27.58  1239.8  72.0  0.0641 
500 500.0  37/4.15 29.05  1377.6  80.0  0.0577 
560 560.0  37/4.39 30.73  1542.9  89.6  0.0515 
630 630.0  61/3.63 32.67  1738.3  100.8  0.0458 
710 710.0  61/3.85 34.65  1959.1  113.6  0.0407 
800 800.0  61/4.09 36.81  2207.4  128.0  0.0361 
900 900.0  61/4.33 38.97  2483.3  144.0  0.0321 
1000 1000.0  61/4.57 41.13  2759.2  160.0  0.0289 
1120 1120.0  91/3.96  43.56  3093.5  179.2  0.0258 
1250 1250.0  91/4.18 45.98  3452.6  200.0  0.0231 
1400 1400.0  91/4.43 48.73  3866.9  224.0  0.0207 
1500 1500.0  91/4.58 50.38  4143.1  240.0  0.0193 
Area No. & Dia. of Wire Approx. Overall
Dia.
Approx.
Weight
Nominal Breaking
Load
Max. DC Resistance
at 20°C
Nominal  Actual
mm2  mm2  No./mm mm kg/km kN Ω/km
16  15.9  7/1.70 5.10  43.0  2.8  1.8022 
25  24.3  7/2.10 6.30  66.0  4.2  1.1810 
35  34.4  7/2.50 7.50  94.0  5.8  0.8333 
50  49.5  7/3.00 9.00  135.0  7.9  0.5787 
50  48.4  19/1.80 9.00  133.0  8.5  0.5951 
70  65.8  19/2.10 10.50  181.0  11.3  0.4372 
95  93.3  19/2.50 12.50  256.0  15.7  0.3085 
120  117.0  19/2.80 14.00  322.0  18.8  0.2459 
150  147.1  37/2.25 15.80  406.0  25.3  0.1960 
185  181.6  37/2.50 17.50  500.0  30.5  0.1588 
240  242.5  61/2.25 20.30  670.0  39.5  0.1191 
300  299.4  61/2.50 22.50  827.0  47.7  0.0965 
400  400.1  61/2.89 26.00  1104.0  60.9  0.0722 
500  499.8  61/3.23 29.10  1379.0  74.7  0.0578 
625  626.2  91/2.96 32.60  1732.0  95.3  0.0462 
800  802.1  91/3.35 36.90  2218.0  118.4  0.0360 
1000  999.7  91/3.74 41.10  2767.0  145.8  0.0289 
Code
Name
Nominal
Area 
No. & Dia. of Wire  Approx.
Overall
Dia.
Approx.
Weight
Nominal
Breaking
Load
Max. DC
Resistance
at 20°C
mm2 No./mm mm kg/km kN Ω/km
Leo 34.4  7/2.50 7.50  94.3  5.7  0.8330 
Leonids 41.6  7/2.75 8.25  113.0  6.7  0.6890 
Libra 49.5  7/3.00 9.00  135.0  8.0  0.5790 
Mars 77.3  7/3.75 11.30  211.0  11.8  0.3700 
Mercury 111.0  7/4.50 13.50  304.0  16.9  0.2580 
Moon 124.0  7/4.75 14.30  339.0  18.9  0.2320 
Neptune 158.0  19/3.25 16.30  433.0  24.7  0.1830 
Orion 183.0  19/3.50 17.50  503.0  28.7  0.1570 
Pluto 210.0  19/3.75 18.80  576.0  31.9  0.1370 
Saturn 262.0  37/3.00 21.00  721.0  42.2  0.1100 
Sirius 307.0  37/3.25 22.80  845.0  48.2  0.0940 
Taurus 337.0  19/4.75 23.80  924.0  51.3  0.0857 
Triton 409.0  37/3.75 26.30  1120.0  62.2  0.0706 
Uranus 506.0  61/3.25 29.30  1400.0  75.2  0.0572 
Ursula 587.0  61/3.50 31.50  1620.0  87.3  0.0493 
Venus 673.0  61/3.75 33.80  1860.0  97.2  0.0429 
Code
Name
Nominal
Area 
No.& Dia. of Wire Approx. Overall
Dia.
Total
 Area 
Approx.
Weight
Nominal Breaking
Load
Max. DC Resistance
at 20°C
mm2 No./mm mm mm2 kg/km kN Ω/km
Midge 22.0  7/2.06 6.18  23.3  64.0  4.0  1.2270 
Ant 50.0  7/3.10 9.30  52.8  145.0  8.3  0.5419 
Fly 60.0  7/3.40 10.20  63.6  174.0  9.9  0.4505 
Wasp 100.0  7/4.39 13.17  106.0  290.0  16.0  0.2702 
Hornet 150.0  19/3.25 16.25  157.6  434.0  25.7  0.1825 
Chafer 200.0  19/3.78 18.90  213.2  587.0  32.4  0.1349 
Cockroach 250.0  19/4.22 21.10  265.7  731.0  40.4  0.1083 
Butterfly 300.0  19/4.65 23.25  322.7  888.0  48.8  0.0892 
Centipede 400.0  37/3.78 26.46  415.2  1145.0  63.1  0.0694 
Code
Name
No.& Dia. of Wire Approx. Overall
Dia.
Total
 Area 
Approx.
Weight
Nominal Breaking
Load
Max. DC Resistance
at 20°C
No./mm mm mm2 kg/km kN Ω/km
Gnat 7/2.21 6.63  26.9 73.0  4.8  1.0643 
Mosquito 7/2.59 7.77  36.9 101.0  6.3  0.7749 
Ladybird 7/2.79 8.37  42.8 117.0  7.3  0.6678 
Bluebottle 7/3.66 10.98  73.6 201.0  11.8  0.3880 
Earwig 7/3.78 11.34  78.6 215.0  12.6  0.3638 
Grasshopper 7/3.91 11.73  84.1 230.0  13.5  0.3400 
Clegg 7/4.17 12.51  95.6 261.0  15.3  0.2989 
Beetle 19/2.67 13.35  106.4 292.0  18.1  0.2701 
Bee 7/4.90 14.70  132 361.0  21.1  0.2165 
Caterpillar 19/3.53 17.65  185.9 511.0  29.8  0.1546 
Spider 19/3.99 19.95  237.6 653.0  38.0  0.1210 
Moth 19/5.00 25.00  373.1 1025.0  59.7  0.0770 
Drone 37/3.58 25.06  372.4 1027.0  59.6  0.0774 
Maybug 37/4.09 28.63  486.1 1341.0  77.8  0.0593 
Scorpion 37/4.27 29.89  529.8 1461.0  84.8  0.0544 
Cicada 37/4.65 32.55  628.3 1733.0  100.5  0.0459 
Code
Name
Nominal Area  No./ Dia. of Wire Approx. Overall
Dia.
Approx.
Weight
Nominal Breaking
Load
Max. DC Resistance
at 20°C
AWG or MCM mm2 No./mm mm kg/km kN Ω/km
Peachbell 6 13.3  7/1.56 4.68  36.6  2.5  2.1477 
Rose 4 21.1  7/1.96 5.88  58.2  3.9  1.3606 
Iris 2 33.6  7/2.47 7.41  92.6  6.0  0.8567 
Pansy 1 42.4  7/2.78 8.34  116.6  7.3  0.6763 
Poppy 1/0.0 53.5  7/3.12 9.36  147.2  8.8  0.5369 
Aster 2/0.0 67.4  7/3.50 10.50  185.7  11.1  0.4267 
Phlox 3/0.0 85.0  7/3.93 11.79  233.9  13.5  0.3384 
Oxlip 4/0.0 107.2  7/4.42 13.26  295.2  17.0  0.2675 
Valerian 250.0  126.7  19/2.91 14.55  348.6  20.7  0.2274 
Sneezewort 250.0  126.7  7/4.80 14.40  348.8  20.1  0.2269 
Laurel 266.8  135.2  19/3.01 15.05  372.2  22.1  0.2125 
Daisy 266.8  135.2  7/4.96 14.88  372.3  21.4  0.2125 
Peony 300.0  152.0  19/3.19 15.95  418.3  24.3  0.1892 
Tulip 336.4  170.5  19/3.38 16.90  469.5  27.3  0.1686 
Daffodil 350.0  177.3  19/3.45 17.25  487.9  28.4  0.1618 
Canna 397.5  201.4  19/3.67 18.35  554.9  31.6  0.1430 
Goldentuft 450.0  228.0  19/3.91 19.55  627.6  35.0  0.1260 
Syringa 477.0  241.7  37/2.88 20.16  664.8  38.6  0.1192 
Cosmos 477.0  241.7  19/4.02 20.10  664.8  37.0  0.1192 
Hyacinth 500.0  253.3  37/2.95 20.65  696.8  40.5  0.1136 
Zinnia 500.0  253.3  19/4.12 20.60  697.1  38.9  0.1134 
Dahlia 556.5  282.0  19/4.35 21.75  775.8  43.3  0.1018 
Mistletoe 556.5  282.0  37/3.12 21.84  775.7  44.3  0.1016 
Meadowsweet 600.0  304.0  37/3.23 22.61  836.3  47.5  0.0948 
Orchid 636.0  322.3  37/3.33 23.31  886.9  50.4  0.0892 
Heuchera 650.0  329.4  37/3.37 23.59  907.4  51.7  0.0871 
Flag 700.0  354.7  61/2.72 24.48  975.8  57.1  0.0811 
Varbena 700.0  354.7  37/3.49 24.43  975.7  55.4  0.0812 
Nasturtium 715.5  362.6  61/2.75 24.75  998.5  58.4  0.0793 
Violet 715.5  362.6  37/3.53 24.71  998.5  56.7  0.0794 
Cattail 750.0  380.0  61/2.82 25.38  1046.0  60.3  0.0754 
Petunia 750.0  380.0  37/3.62 25.34  1046.0  58.6  0.0755 
Lilac 795.0  402.8  61/2.90 26.10  1110.0  63.8  0.0713 
Arbutus 795.0  402.8  37/3.72 26.04  1109.0  61.8  0.0715 
Snapdragon 900.0  456.0  61/3.09 27.81  1256.0  70.8  0.0628 
Cockscomb 900.0  456.0  37/3.96 27.72  1256.0  68.4  0.0631 
Goldenrod 954.0  483.4  61/3.18 28.62  1331.0  75.0  0.0593 
Magnolia 954.0  483.4  37/4.08 28.56  1331.0  72.6  0.0594 
Camellia 1000.0  506.7  61/3.25 29.25  1394.0  78.3  0.0568 
Hawkweed 1000.0  506.7  37/4.18 29.26  1395.0  76.2  0.0566 
Larkspur 1033.5  523.7  61/3.31 29.79  1442.0  81.3  0.0547 
Bluebell 1033.5  523.7  37/4.25 29.75  1441.0  78.8  0.0547 
Marigold 1113.0  564.0  61/3.43 30.87  1553.0  87.3  0.0510 
Hawthorn 1192.5  604.2  61/3.55 31.95  1662.0  93.5  0.0476 
Narsissus 1272.0  644.5  61/3.67 33.03  1774.0  98.1  0.0445 
Columbine 1351.0  694.8  61/3.78 34.02  1884.0  104.0  0.0420 
Carnation 1431.0  725.1  61/3.89 35.01  1997.0  108.0  0.0396 
Gladiolus 1510.5  765.4  61/4.00 36.00  2108.0  114.0  0.0375 
Coreopsis 1590.0  805.7  61/4.10 36.90  2216.0  120.0  0.0357 
Jassamine 1750.0  886.7  61/4.30 38.70  2442.0  132.0  0.0324 
Cowslip 2000.0  1013.0  91/3.77 41.47  2787.0  153.0  0.0286 
Sagebrush 2250.0  1140.0  91/3.99 43.89  3166.0  167.0  0.0255 
Lupine 2500.0  1267.0  91/4.21 46.31  3519.0  186.0  0.0229 
Bitterrot 2750.0  1393.0  91/4.42 48.62  3872.0  205.0  0.0208 
Trillium 3000.0  1520.0  127/3.90 50.70  4226.0  223.0  0.0193 
Bluebonnet 3500.0  1773.0  127/4.22 54.86  4977.0  261.0  0.0165 
Nominal
Area 
Total
Area 
No./Dia. of Wire Approx. Overall
Dia.
Approx.
Weight
Nominal Breaking
Load
Max. DC Resistance
at 20°C
mm2 mm2 No./mm mm kg/km kN Ω/km
35  34.4  7/2.50 7.50  94.0  6.0  0.8333 
50  49.5  7/3.00 9.00  135.3  8.4  0.5787 
70  71.3  7/3.60 10.80  194.9  11.4  0.4019 
95  95.1  7/4.16 12.50  260.2  15.2  0.3010 
120  121.2  19/2.85 14.30  333.2  20.6  0.2374 
150  148.1  19/3.15 15.80  407.0  24.4  0.1943 
185  182.8  19/3.50 17.50  502.4  30.2  0.1574 
210  209.9  193.75  18.80  576.8  33.6  0.1371 
240  238.8  19/4.00 20.00  656.3  38.2  0.1205 
300  297.6  19/3.20 22.40  819.8  49.1  0.0969 
500  502.9  19/4.16 29.10  1385.5  80.5  0.0573